Basic Info.
Application
Construction, Overhead
Voltage
Low and Medium Voltage Cable
Material Shape
Round Wire
Wire Core Material
Red Copper Wire
Product Description
Product Description
Self-supporting LV-ABC Lines
Code: ABC 0.6/1kV, NFA2X, AsXS (n), 1-AES
Standards: HD 626 S1: 1996 Part 4-Section F,
PL WT92/K396, CSN 34761-4F
Construction: Phase Conductors: Aluminum conductors with XLPE insulation.
Neutral Messenger: Aluminum conductors with XLPE insulation.
Application: Aerial Bundled Conductors are used
for tributary networks of power buildings
and their internal networks.
Installation: These cables are not allowed to
be buried, even in conduits.
Dimensions of phase conductors
Cross section | Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity | Breaking load |
(mm²) | min. | max. | nom. | min. | min. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) |
16 | 4,6 | 5,1 | 1,2 | 1,00 | 7,8 | - | 2,60 |
25 | 5,6 | 6,5 | 1,3 | 1,07 | 10,1 | 107 | 4,17 |
35 | 6,6 | 7,5 | 1,3 | 1,07 | 11,0 | 132 | 5,78 |
50 | 7,7 | 8,6 | 1,5 | 1,25 | 12,5 | 165 | 8,45 |
70 | 9,3 | 10,2 | 1,5 | 1,25 | 14,0 | 205 | 11,32 |
95 | 11,0 | 12,0 | 1,7 | 1,50 | 16,1 | - | 15,30 |
120 | 12,5 | 13,5 | 1,8 | 1,60 | 17,6 | - | 20,00 |
150 | 13,9 | 15,0 | 1,8 | 1,60 | 18,8 | - | 25,00 |
* defined for ambient temperature of 35°C and max. conductor temperature of 80°CDimensions of neutral messenger conductorsNumber of phase cores x cross section | Bundle diameter |
+ public lighting conductors | approx. |
+ neutral cross section | |
(mm²) | (mm) |
2 x 16 | 15 |
2 x 25 | 18 |
2 x 35 | 20 |
4 x 16 | 18 |
4 x 25 | 22 |
4 x 35 | 25 |
4 x 50 | 28 |
4 x 70 | 32 |
4 x 70 + 1 x 35 | 36 |
4 x 70 + 2 x 35 | 40 |
4 x 95 | 37 |
4 x 120 | 40 |
4 x 120 + 2 x 35 | 43 |
4 x 150 | 44 |
LV-ABC Lines with Bare Neutral MessengerCode: ABC 0.6/1kV,Standards: HD 626 S1: 1996 Part 5-Section D, AMKA (SFS 2200)Construction: Phase Conductors: Aluminum conductors with XLPE insulation. Neutral Messenger: Aluminum conductors Application: Aerial Bundled Conductors are used for tributary networks of power buildings andtheir internal networks.Installation: These cables are not allowed tobe buried, even in conduits.Dimensions of phase conductorsCross section | Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity | Breaking load |
(mm²) | min. | tolerance | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | |
16 | 4,4 | ±0,05 | 1,4 | - | 7,1 | 7,3 | 70 | - |
25 | 5,9 | ±0,02 | 1,4 | - | 8,3 | 9,1 | 95 | - |
35 | 6,9 | ±0,02 | 1,6 | - | 9,7 | 10,5 | 115 | - |
50 | 8,1 | ±0,25 | 1,6 | - | 10,8 | 11,8 | 140 | - |
70 | 9,7 | ±0,25 | 1,8 | - | 12,8 | 13,8 | 180 | - |
120 | 12,8 | ±0,30 | 2,0 | - | 16,2 | 17,4 | 250 | - |
* defined for ambient temperature of 25°C and max. conductor temperature of 70°CDimensions of neutral messenger conductorsCross section | Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity | Breaking load |
(mm²) | min. | max. | nom. | min. | min. | max. | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | (mm) |
25 | 5,9 | ±0,02 | - | - | 5,5 | 6,3 | - | 7,4 |
35 | 6,9 | ±0,02 | - | - | 6,5 | 7,3 | - | 10,3 |
50 | 8,1 | ±0,25 | - | - | 7,6 | 8,6 | - | 14,2 |
70 | 9,7 | ±0,25 | - | - | 9,2 | 10,2 | - | 20,6 |
95 | 11,4 | ±0,30 | - | - | 10,8 | 12,0 | - | 27,9 |
Dimensions of Cable BundleNumber of phase cores x cross section | Bundle diameter |
+ neutral cross section | approx. |
(mm²) | (mm) |
1 x 16 + 25 | 15 |
3 x 16 + 25 | 22 |
4 x 16 + 25 | 22 |
3 x 25 + 35 | 26 |
4 x 25 + 35 | 26 |
3 x 35 + 50 | 30 |
3 x 50 + 70 | 35 |
3 x 70 + 95 | 41 |
3 x 120 + 95 | 47 |
LV-ABC Lines with Insulated Neutral MessengerCode: ABC 0.6/1kV,Standards: HD 626 S1: 1996 Part 6-Section E, AMKA (SFS 2200)Construction: Aluminum conductors with XLPE insulation. Application: Aerial Bundled Conductors are used for tributary networks of power buildings andtheir internal networks.Installation: These cables are not allowed tobe buried, even in conduits.Dimensions of phase conductorsCross section | Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity | Breaking load |
(mm²) | min. | max. | nom. | min. | min. | max | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | |
16 | 4,6 | 5,1 | 1,2 | - | 7,0 | 7,8 | - | - |
25 | 5,8 | 6,3 | 1,4 | - | 8,6 | 9,4 | 112 | - |
35 | 6,8 | 7,3 | 1,6 | - | 10,0 | 10,9 | 138 | - |
50 | 7,9 | 8,4 | 1,6 | - | 11,1 | 12,0 | 168 | - |
70 | 9,7 | 10,2 | 1,8 | - | 13,3 | 14,2 | 213 | - |
95 | 11,0 | 12,0 | 1,8 | - | 14,6 | 15,7 | 258 | - |
120 | 12,0 | 13,1 | 1,8 | - | 15,6 | 16,7 | 306 | - |
150 | 13,9 | 15,0 | 1,7 | - | 17,3 | 18,6 | 344 | - |
* defined for ambient temperature of 30°C and max. conductor temperature of 90°CDimensions of neutral messenger conductorsCross section | Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity | Breaking load |
(mm²) | min. | max. | nom. | min. | min. | max | (A*) | (kN) |
(mm) | (mm) | (mm) | (mm) | (mm) | |
54,6 | 9,2 | 9,6 | 1,6 | - | 12,3 | 13,0 | - | 16,6 |
70 | 10,0 | 10,2 | 1,5 | - | 12,9 | 13,6 | - | 20,5 |
95 | 12,2 | 12,9 | 1,6 | - | 15,3 | 16,3 | - | 27,5 |
* defined for ambient temperature of 30°C and max. conductor temperature of 90°CDimensions of Cable BundleNumber of phase cores x cross section | Bundle diameter |
+ public lighting conductors | approx. |
+ neutral cross section | |
(mm²) | (mm) |
3 x 25 + 54,6 | 30,0 |
3 x 35 + K x 16 + 54,6 | 33,0 |
3 x 50 + K x 16 + 54,6 | 36,0 |
3 x 70 + K x 16 + 54,6 | 37,5 |
3 x 70 + K x 25 + 54,6 | 40,0 |
3 x 70 + K x 16 + 70 | 41,0 |
3 x 95 + K x 16 + 70 | 44,0 |
3 x 120 + K x 16 + 70 | 46,0 |
3 x 120 + K x 16 + 95 | 47,0 |
3 x 150 + K x 16 + 70 | 48,0 |
3 x 150 + K x 16 + 95 | 49,0 |
Note: K number of public lighting conductors (K can be equal to 0, 1, 2, or 3)
Address:
Wuxi, Jiangsu, China
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics
Company Introduction:
Different kinds of products are available in our company. We′re pleased to get your Inquiry and we will reply you as soon as possible. We stick to the principle of "quality first, service first, continuous improvement and innovation to meet the customers" for the management and "zero defect, zero complaints" as the quality objective.